Description Type CXH-A is designed to heat areas classified as hazardous locations to provide primary or supplementary heating for comfort or freeze protection.
Applications
• Sewage Treatment Plants
• Petrochemical Facilities, Oil Rigs
• Unattended Pumping Stations
• Chemical Storage and Handling Facilities
• Paint Storage Areas
• Grain Elevators
• Coal Preparation Plants
|

|
• Aircraft Servicing Areas
• Oil Refineries
• Areas Containing Metal Dusts
Construction
Cabinet -- 14 gauge steel construction with polyester powder coat paint finish.
Adjustable Louvers -- Control the direction of airflow as needed.
Rugged, Seamless, Copper Heating Elements -- are immersed in the sealed liquid-to-air heat exchanger.
Factory Sealed Heat Exchanger -- Features steel tubes with integral aluminum fins and filled with glycol-water heat transfer fluid.
Safety Pressure Relief Device on the heat exchanger is factory helium leak tested to assure a leak-proof design.
Explosion Proof Ball Bearing Motor -- Permanently lubricated and equipped with built-in thermal overload protection.
Epoxy Coated Aluminum Fan -- Prevents sparking
Features
Pre-Wired Explosion Proof Control Center with magnetic contactor and control circuit transformer.
Quick-acting Manual Reset Cutout Pole, Wall and Ceiling Mounting Kits -- Optional. Recessed threaded fasteners on top of heater for mounting with threaded rods.
Warranty -- Limited Three Year
Optional Features
• Built-in Thermostat 50F to 90 F
• Built-in Manual Disconnect Switch
• Pilot Light
• Fan Selector Switch
Designed for Areas Classified
Low operating temperature for atmospheres having an ignition temperature higher than 165C (329F) code T3B.
• Class I, Group C, D - Divisions 1 & 2
• Class II, Groups E, F, G - Divisions 1 & 2
|