Description
Versatile, high performance VUH heaters can be used for complete primary, supplementary or dual system heating applications in all types of commercial and industrial applica- tions. They direct warm air downward, and are particularly applicable in high bay industrial buildings where columns, towering machinery or warehouse stock would obstruct good horizontal movement of air. Four types of optional diffuser designs can be used to produce a variety of air distribution patterns.
Applications
• Shipping and Receiving Areas
• Power Generating Stations
• Aircraft Hangers
• Warehouses
• Garages
• High Bay Areas |

|
Construction
Cabinet -- Heavy 18 gauge steel, phosphate undercoated for corrosion resistance.
Finish -- An almond powder coat provides a good, clean appearance complementary to modern structures.
Metal Sheath Fintube ® Heating Elements -- The electric heat bank - Chromalox patented metal sheath Fintube ® heating elements. They are shock proof! Heat radiation fins are corrosion-resistant copper-clad steel, furnace brazed to the tubular heating elements to assure superior heat transfer. They don't come loose! Wide spacing prevents clogging. Air is evenly drawn across the circumferential elements preventing hot spots and prolonging element life.
Fan Motor stays cool. A baffle isolates it from the heat radiation of the heating elements. VUH motors run smoothly with low vibration and noise. They're mounted with vibration isolators. Thermal overload protection includes automatic reset. (These totally enclosed units operate on the same line power as the heating bank. Connect direct to the power contactor...no need for separate internal or external motor control components.)
Dynamically Balanced Fan for smooth, quiet operation. Blade pitch is carefully selected so that the volume of air moved results in the optimum discharge air temperature Features
Sub-divided Circuits with Individual Fuse Protection -- Standard on all heaters with a total current draw of 48 Amps or greater and are electrically balanced.
The fuse compartment is conveniently located for easy access.
Integral 120V Control Transformer -- Standard on 480V models, eliminates the need for an external control source (24V optional).
Heavy Duty Magnetic Contactors -- No external contactors are needed; integral, 3-pole, magnetic contactors are standard on all models
Thermal Cutouts open the control circuit and disconnect power to the heating elements if overheating occurs.
Automatic Reset allows the control circuit to reclose and restore power when the temperature returns to normal levels.
Suspension Mount with Hangers or Brackets -- VUH heaters have top angle brackets with four (4) mounting holes for suspension mounting of heaters from ceiling with hangers, or rigid angle brackets. The junction box/control compartment is located on the top housing for overhead wiring. Optional Features
Diffusers -- Radial, Cone, Louver and Anemostat diffusers are available to direct heat coverage.
Fan Only Relay
|